REGMIK product

Single-channel PID regulator for control of shut-off and three-position valves RP1-3

Price
6,000 UAH
Availability
In stock

DISCONTINUED!!!

Replacement RP2-U

The PID regulator RP1-3 is designed for controlling the electric actuator of shut-off regulating (SRV) or three-way valves without considering valve position using PID or pulse laws, and also provides regulation of an input physical quantity according to the proportional-integral-derivative (PID) law in a "heater-cooler" system.

Back to catalog

Specifications

Description

The RP1-3 device is designed for receiving and converting signals coming from resistance temperature detectors (RTDs), thermoelectric converters (TCs), and sensors with standardized output current (AT) and voltage (AN) signals into temperature values (or other physical quantities) and displaying them on built-in digital indicators, while simultaneously controlling the object temperature according to a proportional-integral-derivative (PID) control law.

The RP1-3 allows controlling the electric actuator of a shut-off regulating valve (SRV) or three-way valve without considering its position, using PID or pulse control laws.

The device automatically monitors the status of sensors and whether the measured temperature remains within the established measurement range.

Main functions of the RP1-3:

  • Measurement of temperature, humidity, pressure (or other physical parameters) of various objects via one or two channels using standard sensors:
    Resistance temperature detectors [RTD], thermoelectric converters [TC],
    sensors with standardized output current signals 0..5 mA, 0(4)..20 mA [AT] and
    voltage signals 0..1V, 0..10V [AN];
  • Display of current and set temperature values on built-in LED digital indicators;
  • Regulation of physical quantities according to the proportional-integral-derivative (PID) control law;
  • Control of electric actuators of shut-off regulating (SRV) or three-way valves without accounting for their position, via PID or pulse control laws;
  • Maintaining the object's temperature using the PID control law in a "heater-cooler" system;
  • Ability to change the set temperature values (setpoints) for the PID controller;
  • Capability for automatic tuning of PID controller coefficients;
  • Data exchange with a personal computer via RS-485 interface;
  • The device can be manufactured with one or two four-digit seven-segment indicators;
  • Two power supply options: from 220V AC mains or from 12..24V DC source;
  • LED indication of device operating mode and "Error" signal formation.

Additional information

Specifications

Types of Input Devices
Input Primary Converter
Measurement Range, °C
Modification
Sensor Code
Type
NCS
RTD per DSTU 2858-94
01
TSM 50 W=1.4260
50M
-50..+200
02
TSM 50 W=1.4280
50M
-50..+200
03
TSP 50 W=1.3850
Pt50
-50..+600
04
TSP 50 W=1.3910
50P
-50..+600
05
TSM 100 W=1.4260
100M
-50..+200
06
TSM 100 W=1.4280
100M
-50..+200
07
TSP 100 W=1.3850
Pt100
-50..+600
08
TSP 100 W=1.3910
100P
-50..+600
09
TSP 46 W=1.3910
grp.21
-50..+600
71
TSP 500 W=1.3850
Pt500
-50..+600
72
TSP 1000 W=1.3850
Pt1000
-50..+600
RTD per DSTU 2837-94
10
THK
L
-30..+600
11
THA
K
-50..+1200
12
TJK
J
-30..+850
13
TPP 10
S
0..+1750
15
TPR
B
+200..+1800
16
TVR
A-1
0..+2500
AN
21
Voltage AN1 (0-1V)
-
Set by user
22
Voltage AN2 (0-10V)
23
Voltage AN3 (0-5V)
AT
31
Current AT1 (0-5 mA)
-
Set by user
32
Current AT2 (0-20 mA)
33
Current AT3 (4-20 mA)
Types of Output Devices
Output Device
Load Capacity
Electromagnetic Relay (R)
5A 220V
Triac Optocoupler (OC)
100mA 220V
Transistor Optocoupler (OK)
150mA 80V
Main Technical Specifications of the Temperature Controller
Specification Name
Value
Nominal Supply Voltage, V
220 V AC
12..24 V DC
Permissible Supply Voltage Deviation, %
±10
Power Consumption, W
6
Setpoint, °C
-50..2500
Hysteresis, °C
0..1300
Lower Limit of Tolerance Range, °C
-50..2500
Upper Limit of Tolerance Range, °C
-50..2500
Conversion Characteristic Offset, °C
-99.9..999.9
Cold Junction Compensation, °C
-99.9..99.9
Conversion Characteristic Slope
0.001..9.999
Digital Filter
0.1..99.9
Averaging Time, Number of Measurement Periods
0..9
Output Device Turn-On Delay, s
0..255
Output Device Turn-Off Delay, s
0..255

REGMIK

Downloads

FAQ

Questions and answers

For which sensors is the RP1-3 controller designed?
The RP1-3 device is intended for receiving and converting signals from resistance temperature detectors (RTDs), thermoelectric converters (TCs), and sensors with standardized output current (AT) or voltage (AN) signals into temperature or other physical quantities for further temperature regulation via PID control law.
How does the RP1-3 controller manage valves?
The RP1-3 controls the electric actuator of a shut-off regulating or three-way valve without accounting for valve position, using proportional-integral-derivative (PID) or pulse control laws.
What power supply options are supported by the RP1-3 controller?
The controller has two power supply variants: from 220V AC mains or from a 12..24V DC source, with a permissible deviation of ±10%.
Does the RP1-3 device provide temperature value indication?
The RP1-3 is equipped with built-in digital LED indicators that display current and set temperature values, as well as indication of operating mode and errors.
Is sensor status monitored during operation of the RP1-3 controller?
Yes, the device automatically monitors the status of connected sensors and verifies if the measured temperature is within the established measurement range, ensuring reliable operation.