REGMIK product

Humidity and Temperature Sensors DVT-011, DVTc-011

Price
2,877 UAH
Availability
In stock
SKU
DVT-011

Humidity and temperature sensors are used in climate control systems and process monitoring. DVT sensors can be digital and analog, with digital outputs, RS-485, 4..20 mA or 0..10 V, and various types of metrological characteristics.

Back to catalog

Specifications

Description

The enterprise "REGMIK" manufactures humidity and temperature sensors with digital (DVTc-011) and analog (DVT-011) sensitive elements. In the DVT-011 sensors, the HIH4xxx element is used for humidity measurement, while in the DVTc-011 sensors, the SHTxx element is used. Temperature is measured using temperature sensors from the German company Heraeus.

The humidity and temperature sensors are designed to convert values of relative humidity of the gaseous environment and its temperature (except aggressive gases) into standard electrical signals:

  • analog voltage (measured voltage value at the humidity sensor);
  • I2C - digital sensors;
  • 0-10 V output - for digital and analog sensors;
  • 4-20 mA current - for digital and analog sensors;
  • resistance (temperature value from temperature sensors Pt100, Pt500, or Pt1000) - for analog sensors;
  • RS-485 (ModBus RTU protocol) - for digital sensors.

The scope of application of air humidity sensors is very wide and includes:

  • Maintaining the microclimate within specified limits in production equipped with electronic devices sensitive to humidity;
  • Monitoring humidity in office premises and in everyday life;
  • In the housing and communal services sector — in boiler rooms and water treatment plants, preventing condensation formation;
  • Periodic monitoring helps prevent the appearance of mold and mildew on building walls or in warehouses;
  • Control of technological processes;
  • Control of environmental parameters, etc.

The protective fitting material of the sensors is stainless steel grade 12X18H10T. The DVT-011 and DVTc-011 humidity and temperature sensors do not allow moisture condensation.

The multilayer design of the HIH4xxx sensitive element ensures excellent resistance to most application hazards such as wetting, dust, dirt, oils, and common chemical substances in the environment. Key characteristics of sensors based on the HIH4xxx series elements:

  • Cast thermosetting plastic housing;
  • Almost linear output voltage depending on relative humidity;
  • Interchangeability with laser calibration;
  • Low power consumption design;
  • Increased accuracy;
  • Fast response time;
  • Stable characteristics with low drift;
  • Chemical resistance.

The DVT-011 and DVTc-011 humidity and temperature sensors based on SHTxxx series elements have the following distinctive characteristics:

  • High reliability and long-term stability;
  • Industry-proven technology with more than 10 years of operational experience;
  • Designed for mass production;
  • Optimized for minimal cost;
  • Low signal noise level.

The converter operates stably within the recommended humidity and temperature measurement range. Prolonged exposure to conditions outside the normal range, especially at humidity > 80%, may temporarily increase measurement error. After returning to the normal range, it will slowly return to factory parameters.

Special caution should be exercised when using the converter under high humidity conditions (> 98%) and near the dew point, because wetting of the sensitive element may cause irreversible failure.

Other modifications of humidity sensors are also produced, which can be found here...

You might also be interested in sensors with movable and fixed fittings (standard thread M20x1.5) - DVT-012, DVTc-012.

Additional information

DVTc Characteristics

Working error range of sensors - sht
Type of Metrological Characteristic of Digital DVT
Name of Indicator Type of Metrological Characteristic
1 2
Temperature Sensor
1 CET KCE
2 Range, °C operating from +5 to +60 from +5 to +60
extended from -40 to +100 from -40 to +100
3 Basic error for sub-range, °C, no more than operating ±0.5 ±0.4
extended ±1.8 ±1.5
Relative Humidity Sensor
1 CHEV KCE
2 Range, % operating from 20 to 80 from 20 to 80
extended from 0 to 100 from 0 to 100
3 Basic error for sub-range, %, no more than operating 5 3
extended 7 5

Additional information

DVT Characteristics

Working error range of sensors - hih
Type of Metrological Characteristic of Analog DVT
Name of Indicator Type of Metrological Characteristic
1 2
Temperature Sensor
1 CET Platinum TO, class A or B
2 Range, °C from minus 35 to plus 80
3 Basic error, °C, no more than Class A Class B Class A Class B
±0.5 ±1 ±0.5 ±1
Relative Humidity Sensor
1 CHEV ECEV
2 Range, % from 0 to 100 from 0 to 100
3 Basic error, %, no more than ±5 ±3

REGMIK

Downloads

FAQ

Questions and answers

What are the DVT-011 and DVTc-011 humidity and temperature sensors designed for?
The DVT-011 and DVTc-011 humidity and temperature sensors are designed to convert the relative humidity of gaseous environments and temperature (except aggressive gases) into electrical signals: analog voltage, I2C (for digital), RS-485 (ModBus RTU), 0-10 V, and 4-20 mA current.
Which sensors are used in the DVT-011 and DVTc-011 sensors?
The DVT-011 sensors use the HIH4xxx sensitive element for humidity measurement, while the DVTc-011 sensors use the SHTxxx element. Temperature is measured using Heraeus sensors. Sensors can have analog or digital outputs depending on the model.
What is the operating temperature and humidity range of DVT-011 and DVTc-011 sensors?
DVT-011 sensors have an operating temperature range from -35 to +80 °C, while digital DVTc-011 sensors have a range from -40 to +100 °C. For humidity, they operate in the range 0-100% relative humidity with a basic error up to ±3-7% depending on model and range.
What materials are used to protect the sensors, and are they resistant to environmental exposure?
The protective fitting material of the sensors is stainless steel grade 12X18H10T. The sensor design prevents moisture condensation, and the multilayer HIH4xxx design is resistant to wetting, dust, dirt, oils, and common chemical substances.
What are the operating restrictions of the sensors at high humidity?
At humidity over 80%, measurement errors may temporarily increase. It is especially important to avoid operating the sensor at humidity above 98% and near the dew point, as wetting of the sensitive element can lead to failure.