The RP2 temperature measuring-controller with discrete control is designed to regulate the input physical quantity by two channels according to the PID law. During operation, the device regulates the input quantity using output devices connected through outputs: R, OK, OS.

Back to catalog

Specifications

Description

Description

The RP2 device with discrete control performs regulation of the input physical quantity according to the proportional-integral-derivative (PID) law through two channels.

PID controllers with discrete control are used for precise regulation of the input quantity using contactless actuators (triacs, thyristors, solid-state relays).

RP2 enables the following functions:

  • Measurement of parameters of various objects using standard sensors (resistance temperature detectors (temperature sensors) TSM (50M, 100M) and TSP (50P, 100P, Pt100), thermocouples (THK, THA, TJK, etc.), sensors with unified output signals of current and voltage) by two channels;
  • Display of current and set parameter values on built-in LED digital indicators;
  • Regulation of the physical quantity according to the proportional-integral-derivative (PID) law by two channels;
  • Light indication of the device operating mode;
  • Possibility to change the set value (setpoint) for the PID controller;
  • Data exchange with a personal computer via RS-485 interface;
  • Formation of "Error" signal;
  • Software modification of conversion characteristic parameters.

Manufacturing modifications:
- Panel-mounted execution;
- Power supply from 220V AC mains and from 12..24V DC source;
- Types of input signals: RTD, TC, AN, and AT;
- Types of output devices: R, OK, OS.

Additional information

Characteristics

Types of Input Devices
Input Primary Transducer
Measurement Range, °C
Modification
Sensor Code
Type
Nominal Characteristic
RTD according to DSTU 2858-94
01
TSM 50 W=1.4260
50M
-50..+200
02
TSM 50 W=1.4280
50M
-50..+200
03
TSP 50 W=1.3850
Pt50
-50..+600
04
TSP 50 W=1.3910
50P
-50..+600
05
TSM 100 W=1.4260
100M
-50..+200
06
TSM 100 W=1.4280
100M
-50..+200
07
TSP 100 W=1.3850
Pt100
-50..+600
08
TSP 100 W=1.3910
100P
-50..+600
09
TSP 46 W=1.3910
grp.21
-50..+600
71
TSP 500 W=1.3850
Pt500
-50..+600
72
TSP 1000 W=1.3850
Pt1000
-50..+600
Thermocouples according to DSTU 2837-94
10
THK
L
-30..+600
11
THA
K
-50..+1200
12
TJK
J
-30..+850
13
TPP 10
S
0..+1750
15
TPR
B
+200..+1800
16
TVR
A-1
0..+2500
Analog Voltage (AN)
21
Voltage AN1 (0-1V)
-
User Set
22
Voltage AN2 (0-10V)
23
Voltage AN3 (0-5V)
Analog Current (AT)
31
Current AT1 (0-5 mA)
-
User Set
32
Current AT2 (0-20 mA)
33
Current AT3 (4-20 mA)
Types of Output Devices
Output Device
Load Capacity
Electromagnetic Relay (R)
5A 220V
Optocoupler Triac (OS)
100mA 220V
Optocoupler Transistor (OK)
150mA 80V
Power Triac (S)
2A 220V
Voltage AN1
0..1V
Voltage AN2
0..10V
Voltage AN3
0..5V
Current AT1
0..5mA
Current AT2
0..20mA
Current AT3
4..20mA
Main Technical Specifications of Temperature Controller
Specification Name
Value
Supply Nominal Voltage, V
220AC
12..24 DC
Allowed Power Supply Voltage Deviation, %
±10
Power Consumption, W
6
Set Value (Setpoint), °C
-50..2500
Hysteresis, °C
0..1300
Lower Limit of Tolerance Range, °C
-50..2500
Upper Limit of Tolerance Range, °C
-50..2500
Conversion Characteristic Offset, °C
-99.9..999.9
Cold Junction Temperature Compensation, °C
-99.9..99.9
Conversion Characteristic Slope
0.001..9.999
Digital Filter
0.1..99.9
Averaging Time, Number of Measurement Periods
0..9
Output Device Turn-On Delay, s
0..255
Output Device Turn-Off Delay, s
0..255

Additional information

Modifications

Modifications of Panel-Mounted PID Controllers with Discrete Outputs
T[N1] [N2]RTD,[N3]TC,[N4]ANx,[N5]ATx/ [N6]OK,[N7]R,[N8]OS-2I- RS-485 - IPx – Panel
RP2 – 2AT/2OS-2I- RS-485 – IP24 – Panel
RP 2 2AT 2OS 2I RS-485 IP24 Panel
Device Type: RP - PID controller
[N1] - Number of measurement/control channels: 1, 2, 4, 8
Number and types of input sensors: [N2] - Number of RTD [N3] - Number of TC [N4] - Number of sensors with AN (AN1 - 0 to 1 V; AN2 - 0 to 10 V; AN3 - 0 to 5 V) [N5] - Number of sensors with AT (AT1 - 0 to 5 mA; AT2 - 0 to 20 mA; AT3 - 4 to 20 mA)
Number and types of output devices: [N6] - Number of OK – open collector [N7] - Number of R - relay [N8] - Number of OS - optotriac
Number of indicators: 2I - Two four-digit seven-segment indicators
Communication interface with PC: RS-485
Power supply type: IP1 - Supply from AC mains voltage 90..240V, IP24 - Supply from DC source 12..24V
Enclosure type: Panel