The two-position single-channel controller RD1 1UV/1R performs the following functions: measuring temperature, humidity, pressure (or other physical parameters) of various media and objects.
Used in furnaces of different purposes, drying cabinets, refrigeration equipment, as well as in other areas of activity and for measuring other physical quantities using sensors with standardized output signals.
The device performs two-position regulation of the input physical quantity on two channels, automatically monitors the condition of input sensors, detects measured input quantities outside the set measurement range, verifies correct parameter entry and carries out device calibration.
Main functions:
Works with standard sensors:
thermoresistors [TO],
thermoelectric converters [PT],
thermocouples (THK, THA, THJ, etc.),
sensors with standardized current output signals 0..5 mA, 0 (4)..20 mA [AT] and voltage 0..1 V, 0..10 V [AN]
Displays current measured parameter values on built-in LED digital indicators;
Measures humidity based on the psychrometric method;
Regulates object temperature by two-position control;
Regulates object temperature by three-position control with one channel;
Operates in pulse regulator mode (with the ability to set pulse period and duration);
Light indication of device operating modes;
Data exchange with a personal computer via RS-485 interface (ModBus RTU protocol);
Generates "Error" signal;
Software change of conversion characteristic parameters.
Production modifications:
Housing for mounting on DIN rail;
RS-485 interface (Modbus RTU);
Power supply from AC mains rated 110..220V or DC source rated 12..24V;
Device with one or two four-digit seven-segment indicators;
Type of input sensor: TO, PT, AN, AT or UV (universal input);
Types of output devices: R, OC, OK.
Additional information
Characteristics
Types of Input Devices
Input Primary Converter
Measurement Range, °C
Modification
Sensor Code
Type
Characteristics
RTD (Thermoresistor) according to DSTU 2858-94
01
TSM 50 W=1.4260
50M
-50..+200
02
TSM 50 W=1.4280
50M
-50..+200
03
TSP 50 W=1.3850
Pt50
-50..+600
04
TSP 50 W=1.3910
50P
-50..+600
05
TSM 100 W=1.4260
100M
-50..+200
06
TSM 100 W=1.4280
100M
-50..+200
07
TSP 100 W=1.3850
Pt100
-50..+600
08
TSP 100 W=1.3910
100P
-50..+600
09
TSP 46 W=1.3910
gr.21
-50..+600
71
TSP 500 W=1.3850
Pt500
-50..+600
72
TSP 1000 W=1.3850
Pt1000
-50..+600
RTD according to DSTU 2837-94
10
THK
L
-30..+600
11
THA
K
-50..+1200
12
THJ
J
-30..+850
13
TPP 10
S
0..+1750
15
TPR
B
+200..+1800
16
TVR
A-1
0..+2500
AN (Analog Voltage)
21
Voltage AN1 (0-1V)
-
User-defined
22
Voltage AN2 (0-10V)
23
Voltage AN3 (0-5V)
AT (Analog Current)
31
Current AT1 (0-5 mA)
-
User-defined
32
Current AT2 (0-20 mA)
33
Current AT3 (4-20 mA)
Types of Output Devices
Output Device
Load Capacity
Electromagnetic Relay (R)
5A 220V
Optocoupler Triac (OC)
100mA 220V
Optocoupler Transistor (OK)
150mA 80V
Power Triac (S)
2A 220V
Main Technical Characteristics of the Temperature Controller
What types of sensors does the two-position two-channel RD1 controller support?
The RD1 1UV/1R controller supports the following sensor types: thermoresistors (TO), thermoelectric converters (PT), thermocouples of types THK, THA, THJ, etc., as well as sensors with standardized current output signals (0..5 mA, 0 (4)..20 mA) and voltage (0..1 V, 0..10 V).
What types of output devices and their load capacity does the RD1 controller have?
The controller has output devices of various types, including an electromagnetic relay (5 A, 220 V), optotriac optocoupler (100 mA, 220 V), optotransistor optocoupler (150 mA, 80 V), and power triac (2 A, 220 V).
What power supply options are supported by the RD1 controller?
The controller can be powered either from AC mains 110..220 V or from a DC source 12..24 V. The allowable voltage deviation is ±10%.
What control modes does the RD1 controller support?
The RD1 performs two-position temperature and other physical parameter control on two channels, can operate with three-position control law on one channel, and supports pulse regulator mode with adjustable pulse period and duration.
How are values displayed and is there PC communication in the RD1 controller?
The controller is equipped with built-in LED digital indicators displaying current measured values, has light indication of operating modes, and provides data exchange with a PC via RS-485 interface using ModBus RTU protocol.