REGMIK product

Universal Two-Channel Counter-Timer RP2-T

Price
4,704 UAH
Availability
In stock
SKU
RP2-T

Universal two-channel device RP2-T. PULSE COUNTER / UNIVERSAL TIMER / TIME RELAY.

Back to catalog

Specifications

Description

UNIVERSAL TWO-CHANNEL COUNTER-TIMER
RP2-T

RP2-T

The universal two-channel counter-timer RP2-T is designed to replace an entire series of technological process controllers: pulse counters, universal timers, and time relays.

RS-485 Modbus USB Alarm out Inputs Timer Class 0.15

INFORMATION DISPLAY

LED display RP2-T

The counter-timer uses a high-tech custom LED display that provides the user with clear and intuitive information. The display features a wide viewing angle, and readings are clearly visible even from a great distance in any lighting conditions.

VERSATILITY

Versatility RP2-T

Ability to connect various types of input signal sources — "dry contact", common collector, and others. The device has two analog outputs configurable for the required output range, as well as two discrete outputs and an alarm output.

CONSTRUCTION

Construction RP2-T

The universal two-channel counter-timer RP2-T has an updated case with terminal connections, allowing convenient connection of input sensors and output devices, and ensures reliable mounting in the panel.
The housing is made of polycarbonate, which is flame-retardant.

CERTIFICATION

The universal two-channel counter-timer RP2-T complies with the requirements of the relevant technical regulations:

The device meets the requirements of relevant standards from the national standards list applied:

  • DSTU EN 61326-1:2016, EN 55011:2016/A1:2017/A11:2020 — electrical equipment for measurement, control and laboratory use. Electromagnetic compatibility requirements;
  • DSTU EN 61010-1:2014 — safety requirements for measuring, control and laboratory electrical equipment;
  • DSTU EN 60529:2014 — degrees of protection provided by enclosures IP54.

In addition to the manufacturer's "internal production control" procedure (module A), an accredited conformity assessment body was involved: the State Enterprise "Ukrmetrteststandart" performed voluntary product certification and issued certificate of conformity No. UA.001.30.01054-21 dated 30.09.2021.

The universal two-channel counter-timer RP2-T complies with standards/normative documents and EU Directives: CE, 2014/30/EU (EMC), 2014/35/EU (LVD), 2014/53/EU (RED), 2011/65/EU (RoHS).

UNIVERSAL TWO-CHANNEL COUNTER-TIMER RP2-T: OPERATING MODES

  • forward and reverse pulse counting;
  • operation with encoder;
  • flow meter;
  • frequency meter;
  • tachometer;
  • dosing device;
  • equipment operating time counter;
  • universal timer;
  • time relay.

UNIVERSAL TWO-CHANNEL COUNTER-TIMER RP2-T: TECHNICAL SPECIFICATIONS

Power supply

  • 110...240 V AC, 50/60 Hz;
  • 12...24 V DC.

Internal power supply unit

  • 24 V DC, load capacity 60 mA.

Interfaces

  • RS485 — ModBus RTU protocol;
  • isolated RS485 — ModBus RTU protocol.

Inputs

  • 2 inputs configurable depending on operating mode as counting or enable inputs;
  • 2 run enable inputs for START / STOP / PAUSE / blocking output devices.

Discrete outputs

  • electromechanical relay — 5A, 220 V AC;
  • transistor optocoupler — 100 mA, at 60 V DC;
  • triac optocoupler — 100 mA, at 220 V AC.

Alarm output

  • transistor switch — 100 mA, at 60 V DC.

Analog outputs

  • 0...5 mA, 0...20 mA, 4...20 mA — output signal type configurable by the user.

UNIVERSAL TWO-CHANNEL COUNTER-TIMER RP2-T: FEATURES

The universal two-channel counter-timer RP2-T has the following features:

  • pulse counter operating frequency up to 20 kHz;
  • parameter protection against unauthorized access;
  • saving current operating modes in non-volatile device memory during power loss;
  • ability to configure and run up to 70 universal timer programs simultaneously;
  • universal timer operation with priority: month, week, day of the week, day, hour, minute, second;
  • universal timer operation based on sunrise/sunset;
  • ability to set up to 20 holidays and weekends during which the universal timer does not execute configured operating programs;
  • configuration of up to 40 steps for the time relay;
  • output control via RS-485 interface.

The device can also be supplied in a DIN-rail enclosure, the RP2-M model.

Other devices in the RP2 line:
Universal two-channel meter/controller/pulse counter/time relay/logger RP2-M;
Universal two-channel meter/controller RP2-U.

When designing an RS-485 network, please review the article pdf Button Correct RS-485 Network.

Additional information

Modifications

List of abbreviations: OK – optotransistor, OS – optosimistor, AC – analog current, P – electromagnetic relay

Information about modifications of the universal two-channel device RP2-T-x1x2x3, where:

x1 – output types:

0.– 2OS, 2AC; 1. – 2P, 2AC; 2. – 2OK, 2AC; 3. – 2OS; 4. – 2P; 5. – 2OK; 6. – no outputs.

x2 – interfaces and non-volatile memory power supply:

0. – isolated RS-485 (ModBus RTU protocol); 1. – RS-485 (ModBus RTU protocol).

x3 – type of power supply for the device:

0. – from AC mains nominal voltage 110-240 V AC; 1. – from DC voltage source nominal 12...24 V DC.

REGMIK

Downloads

FAQ

Questions and answers

What is the purpose of the RP2-T counter-timer?
The universal two-channel counter-timer RP2-T is designed to replace a series of technological process controllers such as pulse counters, universal timers, and time relays.
What types of inputs and outputs does the RP2-T have?
The device supports two inputs configurable as count inputs or run enable inputs, and two inputs for START / STOP / PAUSE and blocking output devices. It has multiple output types: electromechanical relay, transistor optocoupler, triac optocoupler, as well as a transistor switch for alarm signaling and two analog outputs with configurable current ranges.
What operating modes does the RP2-T counter-timer support?
The counter supports forward and reverse pulse counting modes, operation with encoder, flow meter, frequency meter, tachometer, dosing device, equipment operating hour counter, universal timer, and time relay modes.
What power supply options does the RP2-T support?
The device can be powered from AC mains 110...240 V or from a DC supply of 12...24 V. The internal power supply unit provides 24 V DC with a load capacity of up to 60 mA.
What are the features of the RP2-T housing design?
The counter housing is made of polycarbonate, which is flame-retardant, and is equipped with convenient terminal connections for reliable mounting in the panel and connection of sensors and output devices.